Skip to main content

AQUATHERM ENERGY Heating element welding

Decisive data for fusion. The general guidelines for hot plate welding according to DVS 2207, part 11 apply.

Pipe outer diameter in mm Warm-up time in sec. DVS Heating time in sec. AQE* Processing time in sec. Cooling time in min. Welding depth in mm
20 5 8 4 2 14,5
25 7 11 4 2 16,0
32 8 12 6 4 18,0
40 12 18 6 4 20,5
50 18 27 6 4 23,5
63 24 36 8 6 27,5
75 30 45 8 8 30,0
90 40 60 8 8 33,0
110 50 75 10 8 37,0
125 60 90 10 8 40,0

NOTE: sec. AQE* Following DVS 2207, part 11, the heating times (sec. AQT) should be used at ambient temperatures below +5 °C. Pipes in diameters 160 - 630 mm are butt-welded.